APC UPS SNMP

Macros used

NameValue
{$BATTERY.CAPACITY.MIN.WARN}50
{$BATTERY.TEMP.MAX.WARN}55
{$SNMP.TIMEOUT}5m
{$TIME.PERIOD}15m
{$UPS.INPUT_FREQ.MAX.WARN}50.3
{$UPS.INPUT_FREQ.MIN.WARN}49.7
{$UPS.INPUT_VOLT.MAX.WARN}243
{$UPS.INPUT_VOLT.MIN.WARN}197
{$UPS.OUTPUT.MAX.WARN}80

Items collected

NameDescriptionTypeIntervalKey and additional info
Battery capacityMIB: PowerNet-MIB The remaining battery capacity expressed as percentage of full capacity.SNMP_AGENT

-

battery.capacity[upsHighPrecBatteryCapacity]
External battery packs countMIB: PowerNet-MIB The number of external battery packs connected to the UPS. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME.SNMP_AGENT1hbattery.external_packs_count[upsAdvBatteryNumOfBattPacks]
Battery last replace dateMIB: PowerNet-MIB The date when the UPS system's batteries were last replaced in mm/dd/yy (or yyyy) format. For Smart-UPS models, this value is originally set at the factory. When the UPS batteries are replaced, this value should be reset by the administrator. For Symmetra PX 250/500 this OID is read-only and is configurable in the local display only.SNMP_AGENT1hbattery.last_replace_date[upsBasicBatteryLastReplaceDate]
Battery replace indicatorMIB: PowerNet-MIB Indicates whether the UPS batteries need replacement.SNMP_AGENT

-

battery.replace_indicator[upsAdvBatteryReplaceIndicator]
Battery runtime remainingMIB: PowerNet-MIB The UPS battery run time remaining before battery exhaustion.SNMP_AGENT

-

battery.runtime_remaining[upsAdvBatteryRunTimeRemaining]
Battery statusMIB: PowerNet-MIB The status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is not restored. The amount of run time in reserve at the time of low battery can be configured by the upsAdvConfigLowBatteryRunTime. A batteryInFaultCondition(4)value indicates that a battery installed has an internal error condition.SNMP_AGENT

-

battery.status[upsBasicBatteryStatus]
Battery temperatureMIB: PowerNet-MIB The current internal UPS temperature in Celsius. Temperatures below zero read as 0.SNMP_AGENT

-

battery.temperature[upsHighPrecBatteryTemperature]
Battery voltageMIB: PowerNet-MIB The actual battery bus voltage in Volts.SNMP_AGENT

-

battery.voltage[upsHighPrecBatteryActualVoltage]
Input fail causeMIB: PowerNet-MIB The reason for the occurrence of the last transfer to UPS battery power. The variable is set to: - noTransfer(1) -- if there is no transfer yet. - highLineVoltage(2) -- if the transfer to battery is caused by an over voltage greater than the high transfer voltage. - brownout(3) -- if the duration of the outage is greater than five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - blackout(4) -- if the duration of the outage is greater than five seconds and the line voltage is between 40% of the rated output voltage and ground. - smallMomentarySag(5) -- if the duration of the outage is less than five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - deepMomentarySag(6) -- if the duration of the outage is less than five seconds and the line voltage is between 40% of the rated output voltage and ground. The variable is set to - smallMomentarySpike(7) -- if the line failure is caused by a rate of change of input voltage less than ten volts per cycle. - largeMomentarySpike(8) -- if the line failure is caused by a rate of change of input voltage greater than ten volts per cycle. - selfTest(9) -- if the UPS was commanded to do a self test. - rateOfVoltageChange(10) -- if the failure is due to the rate of change of the line voltage.SNMP_AGENT

-

input.fail[upsAdvInputLineFailCause]
Input frequencyMIB: PowerNet-MIB The current input frequency to the UPS system in Hz.SNMP_AGENT

-

input.frequency[upsHighPrecInputFrequency]
Input voltageMIB: PowerNet-MIB The current utility line voltage in VAC.SNMP_AGENT

-

input.voltage[upsHighPrecInputLineVoltage]
Output currentMIB: PowerNet-MIB The current in amperes drawn by the load on the UPS.SNMP_AGENT

-

output.current[upsHighPrecOutputCurrent]
Output loadMIB: PowerNet-MIB The current UPS load expressed as percentage of rated capacity.SNMP_AGENT

-

output.load[upsHighPrecOutputLoad]
Output statusMIB: PowerNet-MIB The current state of the UPS. If the UPS is unable to determine the state of the UPS this variable is set to unknown(1). During self-test most UPSes report onBattery(3) but some that support it will report onBatteryTest(15). To determine self-test status across all UPSes, refer to the upsBasicStateOutputState OID.SNMP_AGENT

-

output.status[upsBasicOutputStatus]
Output voltageMIB: PowerNet-MIB The output voltage of the UPS system in VAC.SNMP_AGENT

-

output.voltage[upsHighPrecOutputVoltage]
SNMP traps (fallback)The item is used to collect all SNMP traps unmatched by other snmptrap itemsSNMP_TRAP

-

snmptrap.fallback
System contact detailsMIB: SNMPv2-MIB The textual identification of the contact person for this managed node, together with information on how to contact this person. If no contact information is known, the value is the zero-length string.SNMP_AGENT15msystem.contact[sysContact.0]
System descriptionMIB: SNMPv2-MIB A textual description of the entity. This value should include the full name and version identification of the system's hardware type, software operating-system, and networking software.SNMP_AGENT15msystem.descr[sysDescr.0]
System locationMIB: SNMPv2-MIB The physical location of this node (e.g., `telephone closet, 3rd floor'). If the location is unknown, the value is the zero-length string.SNMP_AGENT15msystem.location[sysLocation.0]
ModelMIB: PowerNet-MIB The UPS model name (e.g. 'APC Smart-UPS 600').SNMP_AGENT15msystem.model[upsBasicIdentModel]
System nameMIB: SNMPv2-MIB An administratively-assigned name for this managed node.By convention, this is the node's fully-qualified domain name. If the name is unknown, the value is the zero-length string.SNMP_AGENT15msystem.name[sysName.0]
System object IDMIB: SNMPv2-MIB The vendor's authoritative identification of the network management subsystem contained in the entity. This value is allocated within the SMI enterprises subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determiningwhat kind of box' is being managed. For example, if vendorFlintstones, Inc.' was assigned the subtree1.3.6.1.4.1.4242, it could assign the identifier 1.3.6.1.4.1.4242.1.1 to its `Fred Router'.SNMP_AGENT15msystem.objectid[sysObjectID.0]
Serial numberMIB: PowerNet-MIB An 8-character string identifying the serial number of the UPS internal microprocessor. This number is set at the factory. NOTE: This number does NOT correspond to the serial number on the rear of the UPS.SNMP_AGENT15msystem.sn[upsAdvIdentSerialNumber]
UptimeMIB: SNMPv2-MIB The time (in hundredths of a second) since the network management portion of the system was last re-initialized.SNMP_AGENT30ssystem.uptime[sysUpTime.0]
SNMP agent availabilityAvailability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list. Possible value: 0 - not available 1 - available 2 - unknownINTERNAL

-

zabbix[host,snmp,available]

Triggers

NameDescriptionExpressionPriorityDependencies
Battery has low capacity

-

last(/APC UPS SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN}HIGH ⛔Battery capacity
Battery needs replacementA battery installed has an internal error condition.last(/APC UPS SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2HIGH ⛔Battery replace indicator
Battery has an internal error conditionA battery installed has an internal error condition.last(/APC UPS SNMP/battery.status[upsBasicBatteryStatus])=4AVERAGE ⚠Battery status
Battery is LowThe UPS will be unable to sustain the current load, and its services will be lost if power is not restored.last(/APC UPS SNMP/battery.status[upsBasicBatteryStatus])=3AVERAGE ⚠Battery status
Battery has high temperature

-

min(/APC UPS SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}HIGH ⛔Battery temperature
Unacceptable input frequency

-

min(/APC UPS SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN})HIGH ⛔Input frequency
Unacceptable input voltage

-

min(/APC UPS SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN})HIGH ⛔Input voltage
Output load is highA battery installed has an internal error condition.min(/APC UPS SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN}HIGH ⛔Output load
UPS is Emergency Static Bypass

-

last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=16AVERAGE ⚠Output status
UPS is Hardware Failure Bypass

-

last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=10AVERAGE ⚠Output status
UPS is Off

-

last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=7AVERAGE ⚠Output status
UPS is on battery

-

last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=3AVERAGE ⚠Output status
UPS is on Smart Boost

-

last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=4AVERAGE ⚠Output status
UPS is On Smart Trim

-

last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=12AVERAGE ⚠Output status
UPS is Rebooting

-

last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=8AVERAGE ⚠Output status
UPS is Sleeping Until Power Return

-

last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=11AVERAGE ⚠Output status
UPS is Software Bypass

-

last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=6AVERAGE ⚠Output status
UPS is Switched Bypass

-

last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=9AVERAGE ⚠Output status
UPS is Timed Sleeping

-

last(/APC UPS SNMP/output.status[upsBasicOutputStatus])=5AVERAGE ⚠Output status
System name has changedSystem name has changed. Ack to close.last(/APC UPS SNMP/system.name[sysName.0],#1)<>last(/APC UPS SNMP/system.name[sysName.0],#2) and length(last(/APC UPS SNMP/system.name[sysName.0]))>0INFO 🔔System name
has been restartedUptime is less than 10 minutes.last(/APC UPS SNMP/system.uptime[sysUpTime.0])<10mWARNING 📢Uptime
No SNMP data collectionSNMP is not available for polling. Please check device connectivity and SNMP settings.max(/APC UPS SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0WARNING 📢SNMP agent availability

Discovery rule №1

NameDescriptionTypeIntervalKey and additional info
External bad battery packs discoveryDiscovery of the number of external defective battery packs.SNMP_AGENT1hbattery.packs.bad.discovery

Item prototypes

NameDescriptionTypeIntervalKey and additional info
{#SNMPINDEX}: External battery packs badMIB: PowerNet-MIB The number of external battery packs connected to the UPS that are defective. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME.SNMP_AGENT15mbattery.external_packs_bad[upsAdvBatteryNumOfBadBattPacks.{#SNMPINDEX}]

Discovery rule №2

NameDescriptionTypeIntervalKey and additional info
External battery packs discovery

-

SNMP_AGENT1hbattery.packs.discovery

Item prototypes

NameDescriptionTypeIntervalKey and additional info
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery estimated replace dateMIB: PowerNet-MIB The battery cartridge estimated battery replace date.SNMP_AGENT1hbattery.estimated_replace_date[upsHighPrecBatteryPackCartridgeReplaceDate.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge healthMIB: PowerNet-MIB The battery cartridge health. bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement cartridge bit 2 Battery lifetime exceeded, replace battery bit 3 Battery lifetime near end acknowledged, order replacement cartridge bit 4 Battery lifetime exceeded acknowledged, replace battery bit 5 Battery measured lifetime near end, order replacement cartridge bit 6 Battery measured lifetime near end acknowledged, order replacement cartridgeSNMP_AGENT

-

battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery statusMIB: PowerNet-MIB The battery cartridge status. bit 0 Disconnected bit 1 Overvoltage bit 2 NeedsReplacement bit 3 OvertemperatureCritical bit 4 Charger bit 5 TemperatureSensor bit 6 BusSoftStart bit 7 OvertemperatureWarning bit 8 GeneralError bit 9 Communication bit 10 DisconnectedFrame bit 11 FirmwareMismatchSNMP_AGENT

-

battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery temperatureMIB: PowerNet-MIB The battery pack temperature in Celsius.SNMP_AGENT

-

battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial numberMIB: PowerNet-MIB The battery pack serial number.SNMP_AGENT15msystem.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}]

Trigger prototypes

NameDescriptionExpressionPriorityDependencies
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okayThe battery cartridge health. bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement cartridge bit 2 Battery lifetime exceeded, replace battery bit 3 Battery lifetime near end acknowledged, order replacement cartridge bit 4 Battery lifetime exceeded acknowledged, replace battery bit 5 Battery measured lifetime near end, order replacement cartridge bit 6 Battery measured lifetime near end acknowledged, order replacement cartridgefind(/APC UPS SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1WARNING 📢{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okayThe battery cartridge status: bit 0 Disconnected bit 1 Overvoltage bit 2 NeedsReplacement bit 3 OvertemperatureCritical bit 4 Charger bit 5 TemperatureSensor bit 6 BusSoftStart bit 7 OvertemperatureWarning bit 8 GeneralError bit 9 Communication bit 10 DisconnectedFrame bit 11 FirmwareMismatchfind(/APC UPS SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0WARNING 📢{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature

-

min(/APC UPS SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN}HIGH ⛔{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery temperature

Discovery rule №3

NameDescriptionTypeIntervalKey and additional info
External sensor port 1 discoveryuioSensorStatusTableSNMP_AGENT1hexternal.sensor1.discovery

Item prototypes

NameDescriptionTypeIntervalKey and additional info
{#EXTERNAL_SENSOR1_NAME}: Humidity sensorMIB: PowerNet-MIB The sensor's current humidity reading - a relative humidity percentage. -1 indicates an invalid reading due to either a sensor that doesn't read humidity or lost communications.SNMP_AGENT

-

external.sensor.humidity[uioSensorStatusHumidity.1.{#SNMPINDEX}]
{#EXTERNAL_SENSOR1_NAME}: Sensor alarm statusMIB: PowerNet-MIB The alarm status of the sensor. Possible values: uioNormal (1), uioWarning (2), uioCritical (3), sensorStatusNotApplicable (4)SNMP_AGENT

-

external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}]
{#EXTERNAL_SENSOR1_NAME}: Temperature sensorMIB: PowerNet-MIB The sensor's current temperature reading in Celsius. -1 indicates an invalid reading due to lost communications.SNMP_AGENT

-

external.sensor.temperature[uioSensorStatusTemperatureDegC.1.{#SNMPINDEX}]

Trigger prototypes

NameDescriptionExpressionPriorityDependencies
{#EXTERNAL_SENSOR1_NAME}: Sensor has status CriticalThe external sensor has returned a value greater than the critical threshold.last(/APC UPS SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3HIGH ⛔{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status
{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not ApplicableThe external sensor does not work or is not connected.last(/APC UPS SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4INFO 🔔{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status
{#EXTERNAL_SENSOR1_NAME}: Sensor has status WarningThe external sensor has returned a value greater than the warning threshold.last(/APC UPS SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2AVERAGE ⚠{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status

Discovery rule №4

NameDescriptionTypeIntervalKey and additional info
External sensor port 2 discoveryuioSensorStatusTableSNMP_AGENT1hexternal.sensor2.discovery

Item prototypes

NameDescriptionTypeIntervalKey and additional info
{#EXTERNAL_SENSOR2_NAME}: Humidity sensorMIB: PowerNet-MIB The sensor's current humidity reading - a relative humidity percentage. -1 indicates an invalid reading due to either a sensor that doesn't read humidity or lost communications.SNMP_AGENT

-

external.sensor.humidity[uioSensorStatusHumidity.2.{#SNMPINDEX}]
{#EXTERNAL_SENSOR2_NAME}: Sensor alarm statusMIB: PowerNet-MIB The alarm status of the sensor. Possible values: uioNormal (1), uioWarning (2), uioCritical (3), sensorStatusNotApplicable (4)SNMP_AGENT

-

external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}]
{#EXTERNAL_SENSOR2_NAME}: Temperature sensorMIB: PowerNet-MIB The sensor's current temperature reading in Celsius. -1 indicates an invalid reading due to lost communications.SNMP_AGENT

-

external.sensor.temperature[uioSensorStatusTemperatureDegC.2.{#SNMPINDEX}]

Trigger prototypes

NameDescriptionExpressionPriorityDependencies
{#EXTERNAL_SENSOR2_NAME}: Sensor has status CriticalThe external sensor has returned a value greater than the critical threshold.last(/APC UPS SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3HIGH ⛔{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status
{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not ApplicableThe external sensor does not work or is not connected.last(/APC UPS SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4INFO 🔔{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status
{#EXTERNAL_SENSOR2_NAME}: Sensor has status WarningThe external sensor has returned a value greater than the warning threshold.last(/APC UPS SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2AVERAGE ⚠{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status

Discovery rule №5

NameDescriptionTypeIntervalKey and additional info
Input phases discoveryThe input phase identifier. OID upsPhaseInputPhaseIndex.1.1SNMP_AGENT1hinput.phases.discovery

Item prototypes

NameDescriptionTypeIntervalKey and additional info
{#PHASEINDEX}: Phase input currentMIB: PowerNet-MIB The input current in 0.1 amperes, or -0.1 if it's unsupported by this UPS.SNMP_AGENT

-

phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}]
{#PHASEINDEX}: Phase input voltageMIB: PowerNet-MIB The input voltage in VAC, or -1 if it's unsupported by this UPS.SNMP_AGENT

-

phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}]

Trigger prototypes

NameDescriptionExpressionPriorityDependencies
{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage

-

min(/APC UPS SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}HIGH ⛔{#PHASEINDEX}: Phase input voltage

Discovery rule №6

NameDescriptionTypeIntervalKey and additional info
Output phases discoveryThe output phase identifier. OID upsPhaseOutputPhaseIndex.1.1SNMP_AGENT1houtput.phases.discovery

Item prototypes

NameDescriptionTypeIntervalKey and additional info
{#PHASEINDEX}: Phase output currentMIB: PowerNet-MIB The output current in 0.1 amperes drawn by the load on the UPS, or -1 if it's unsupported by this UPS.SNMP_AGENT

-

phase.output.current[upsPhaseOutputCurrent.1.1.{#PHASEINDEX}]
{#PHASEINDEX}: Phase output load, %MIB: PowerNet-MIB The percentage of the UPS load capacity in VA at redundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this UPS.SNMP_AGENT

-

phase.output.load.percent[upsPhaseOutputPercentLoad.1.1.{#PHASEINDEX}]
{#PHASEINDEX}: Phase output voltageMIB: PowerNet-MIB The output voltage in VAC, or -1 if it's unsupported by this UPS.SNMP_AGENT

-

phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}]

Trigger prototypes

NameDescriptionExpressionPriorityDependencies
{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage

-

min(/APC UPS SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}HIGH ⛔{#PHASEINDEX}: Phase output voltage